SPD for Equipment

Part Number

Configured Part Number is shown.

Part Number
LT-C12G801W
LT-C14G801W
LT-C32G801W
LT-C34G801W
LT-C35G102W
Part NumberVolume DiscountDays to Ship RoHSVoltage Maximum Continuous Operational Voltage Voltage protection level Direct current discharge starting voltage Voltage when starting operations Number of phases, number of wires
Available

6 Days or more

10200VAC275V1.5kVBetween line and ground 800V ± 20%Line 540V ± 10%Single-phase 2-line
Available

6 Days or more

-400VLine AC480V/ ground 280V1.8kVBetween line and ground 800V ± 20%Line 940V ± 10%Single-phase 2-line
Available

6 Days or more

10200VAC275V1.5kVBetween line and ground 800V ± 20%Line 540V ± 10%Three-phase three-line
Available

6 Days or more

-400VY wire connection AC 480 V/△ wire connection 280V1.8kVBetween line and ground 800V ± 20%Line 940V ± 10%Three-phase three-line
Available

6 Days or more

-500VY wire connection AC 550 V/△ wire connection 320 V2.0kVBetween line and ground 1000 V ± 20%Line 1100V ± 10%Three-phase three-line

Loading...

  1. 1

Basic Information

Application Power supply Model Integrated type Mounting method Cord direct removal
Class, category Class II Representative standards UL / CUL / TUV / CSA Dimension vertical(mm) 33.5
Dimension width(mm) 38 Dimension depth(mm) 28 Nominal Discharge Current (8/20 μs) 2500A
Maximum Discharge Current (8/20 μs) 5000A